Products Cathodic Protector Arrestors

Delta SOV Arrestor for AC or DC applications to 120 Volts. Stainless Steel mounting ears connect directly to line studs.

LA101ME




100 Series Specifications

Type of Design Silicon Oxide Varistor
Maximum current 25,000 amps
Maximum energy 1,000 joules per pole
Maximum number of surges Unlimited
Response time one milliamp test 5 nanoseconds
Response time to clamp 10,000 amps 10 nanoseconds
Response time to clamp 50,000 amps 25 nanoseconds
Leak current at double the rated voltage none
Case material PVC
Conduction Characteristics
8 x 20 microsecond wave shape - ANSI IEEE NEMA Standard
Discharge Current 5000 A 10000 A 20000 A 40000 A 60000 A 80000 A 100000 A AMPERAGE
LA 602 450 V 920 V 1040 V 1500 V 2300 V 4000 V 5000 V CLAMPING VOLTAGE LINE TO NEUTRAL
LA 302 DC 240 V 480 V 840 V 1300 V 2000 V CLAMPING VOLTAGE LINE TO NEUTRAL
Electrical work is hazardous. Bad connections can result in fire, injury or death. Installation must only be done by qualified electricians.

In the event that a lightning discharge is so powerful that something has to be destroyed, the arrestor will take the damage. When sufficient heat and stress causes failure, a one inch hole will open at the bottom of the enclosure. Hot silica and plastic bits will be expelled. Installing the arrestor in any approved electrical box will prevent accidental contact with a damaged unit.