Industrial Arrestors
Rapid Response, High Current Delta ArrestorsTM
For Industrial Use Help Prevent Voltage Surge and Lightning Damage to Motors and Control Equipment.



600 Series Specifications

Type of Design Silicon Oxide VaristorTM
Maximum current 100,000 amps
Maximum energy

3,000 joules per pole

Maximum number of surges Unlimited
Response time one milliamp test 5 nanoseconds
Response time to clamp 10,000 amps 10 nanoseconds
Response time to clamp 50,000 amps 25 nanoseconds
Leak current at double the rated voltage none
Leads 36" #12 THHN
Case material PVC
Locknut and Washer Furnished

Conduction Characteristics

8 x 20 microsecond wave shape
ANSI IEEE NEMA Standard
Discharge Current 5000 A 10000 A 20000 A 40000 A 60000 A 80000 A 100000 A
Clamping Voltage
(Line to Neutral)
450 V 920 V 1040 V 1500 V 2300 V 4000 V 5000 V
Unlimited Operations One Operation
DELTA LIGHTNING ARRESTORS,™ INC. P.O. BOX 750
BIG SPRING, TX 79721
432-267-1000
www.deltala.com
[email protected]


LA 601

LA 602

LA 603

Weather Proof N-4
Case Dimessions:
2 1/4" Diameter
4 1/2" High

LA601 - For 440-600 Volt Single
Phase 2 Wire Service

Rated voltage 240-480-600 Volt, two wire service. Used when one hot wire of a three phase system is to be protected; one wire for a control circuit, or three arrestors for protecting three phases.

INSTALLATION:
Fasten arrestor in place. Use a Delta mounting bracket, part # MB, a pipe strap, or a knockout hole. Connect the black wire to the hot line at any convenient point load-side of an existing fuse or circuit breaker. Connect the white wire to an existing ground system and the grounded metal frame work of the equipment to be protected, or make a ground source per NEC Article 250.

Weather Proof N-4
Case Dimessions:
2 1/4" Diameter
4 1/2" High

LA602 - For 440-600 Volt Single
Phase, 3 Wire Service.

Rated voltage 240-480-600 Volt, three wire service. Used when two hot wires of a single or three phase system are to be protected; two wires used to feed a control circuit transformer, or two hots supplying a 480V load such as a street light or a single phase motor.

INSTALLATION:
Fasten arrestor in place. Use a Delta mounting bracket, part # MB, a pipe strap, or a knockout hole. Connect the black wires to the hot line at any convenient point load-side of an existing fuse or circuit breaker. Connect the white wire to an existing ground system and the grounded metal frame work of the equipment to be protected, or make a ground source per NEC Article 250.

Weather Proof N-4
Case Dimessions:
2 1/4" Diameter
4 1/2" High

LA603 - For 440-600 Volt 3 or 4
Wire Service

Rated voltage 240-480-600 Volt, three or four wire service. Used when three hot wires of a three phase system are to be protected.

INSTALLATION:
Fasten arrestor in place. Use a Delta mounting bracket, part # MB, a pipe strap, or a knockout hole. Connect the black wires to the hot line at any convenient point load-side of an existing fuse or circuit breaker. Connect the white wire to an existing ground system and the grounded metal frame work of the equipment to be protected, or make a ground source per NEC Article 250.

LA601 Pricing

LA602 Pricing

LA603 Pricing


Electrical work is hazardous. Bad connections can result in fire, injury or death. Installation must only be done by qualified electricians.

In the event that a lightning discharge is so powerful that something has to be destroyed, the arrestor will take the damage. When sufficient heat and stress causes failure, a one inch hole will open at the bottom of the enclosure. Hot silica and plastic bits will be expelled. Installing the arrestor in any approved electrical box will prevent accidental contact with a damaged unit.


 