Cathodic Protector Arrestors
Delta SOV Arrestor for AC or DC applications to 120 Volts. Stainless Steel mounting ears connect directly to line studs.


100 Series Specifications

   
Type of design Silicon Oxide Varistor  
Maximum current 25,000 amps

Maximum energy 1000 joules
Maximum number of surges Unlimited
Response time one milliamp test 5 nanoseconds
Response time to clamp 10,000 amps 10 nanoseconds

Stud Centers

|------------2.4"-----------|

Response time to clamp 25,000 amps 25 nanoseconds

Leak current at double the rated voltage None
Case material PVC  
LA602: 480V three wire unit
to protect the AC circuit

LA302DC: 0-500V three wire
unit to protect the DC circuit
18 inch leads

Weatherproof Enclosure
2 1/4"High, 2 1/4" Diameter
LA302DC
LA104: Combination Unit,
Combines LA602 with
LA 302 DC in one enclosure
36 inch leads

Weatherproof Enclosure
4 1/2"High, 2 1/4" Diameter
LA 602 & LA 104


Conduction Characteristics

8 x 20 microsecond wave shape
ANSI IEEE NEMA Standard
Discharge Current 5000 A 10000 A 20000 A 40000 A 60000 A 80000 A 100000 A AMPERAGE
LA 602 450 V 920 V 1040 V 1500 V 2300 V 4000 V 5000 V CLAMPING VOLTAGE
LINE TO NEUTRAL
LA 302 DC 240 V 480 V 840 V 1300 V 2000 V     CLAMPING VOLTAGE
LINE TO NEUTRAL