Delta Water Well Arrestor |
300 Series Specifications | Nipple 1/2"
Thread![]() DIMENSIONS: 4-1/2" High, 2-1/4" Diameter | |
Type of Design | Silicon Oxide Varistor | |
Maximum current | 100,000 amps | |
Maximum energy | 3000 Joules per pole | |
Maximum Number of Surges | Unlimited | |
Response Time one Milliamp Test | 5 nanoseconds | |
Response Time to Clamp 10,000 amps | 10 nanoseconds | |
Response Time to Clamp 25,000 amps | 25 nanoseconds | |
Leak Current at Double the Rated Voltage | None | |
Leads | 36" 3kV#12 Str | |
Case Material | PVC | |
Locknut and Washer furnished | 3/4" - 1 1/2" | |
Category B & C and Type 1 & 2 |
Simple Installation | |||||||
Connect the black wires to the hot lines at a convenient point load side of th fuses (breakers). Connect the white wire to the ground, and/or grounded neutral. To protect pumps it is important that a conductor is connected fromt he arrestor ground to the actual steel frame of the motor/pump. A wire from the arrestor ground point to the mteal tubing will do. If the tubing is plastic, connect to the metal casing, or next closest grounded metal. | |||||||
Conduction Characteristics |
8 x 20 microsecond wave shape ANSI IEEE NEMA | ||||||
Discharge Current | 5000 A | 10000 A | 20000 A | 40000 A | 60000 A | 80000 A | 100000 A |
Clamping Voltage (Line to Neutral) |
240 V | 480 V | 840 V | 1300 V | 2000 V | 3000 V | 4000 V |
Unlimited Operations | One Operation | ||||||